PELLET STOVES 8 PS45 CLASSIC 151211-24
Fig. #4
M
K
I
A
V
G
G
H
A
J
V
G
A
B
C
A
V
V
A
V
B
F
B
L
V
E
V
V
V
D
AIR SUPPLY INLET
VENT TERMINAL
GAS METER
FIXED
CLOSED
FIXED
CLOSED
OPEN-
ABLE
OPEN-
ABLE
AREA WHERE TERMINAL
IS NOT PERMITTED
Vent Terminal Minimum Clearances
ALL CLEARANCES ARE MINIMUMS
A= *12 inches (30 cm) Clearances above non combustible grade
*24 inches (60 cm) Clearances above grass, top of plants, wood, combustible veranda, porch, deck, or balcony
B= *48 inches (120 cm) Clearance beside or below a window or door that may be opened
*18 inches (45 cm) If Fresh Air is Installed to the Unit - Clearance beside or below a window or door that
may be opened
*12 inches (30 cm) Above a window or door that opens
C= 12 inches (30 cm) Clearance to permanently closed window recommended to prevent condensation on window
D= 36 inches (76 cm) Vertical clearance to ventilated soffit located above the terminal within a horizontal distance
of 2 feet (60 cm) from the edge of the terminal
18 inches (45 cm) If Fresh Air Installed to Unit - Vertical clearance to ventilated soffit located above the terminal
within a horizontal distance of 2 feet (60 cm) from the edge of the terminal
E= 12 inches (30 cm) Clearance to unventilated soffit
F= 12 inches (30 cm) Clearance to outside corner
G= 12 inches (30 cm) Clearance to inside corner
H= 3 feet (90 cm) *Not to be installed above a meter/regulator assembly within 3 feet (90 cm) horizontally from
the center-line of the regulator
I= *6 feet (1.8 m) Clearance to service regulator vent outlet
J= *4 feet(1.2 m) Clearance to non mechanical air supply inlet to building or the combustion air inlet to any
other appliance
12 inches (30 cm) If Fresh Air installed to Unit - Clearance to non mechanical air supply inlet to building or the
combustion air inlet to any other appliance
K= *10 feet (3.1 m) Clearance to a mechanical air supply inlet
L= 7 feet (2.1 m) ^ Clearance above paved side-walk or a paved driveway located on public property
M= **12 inches (30 cm) Clearance under veranda, porch, deck, or balcony
^ a vent shall not terminate directly above a side-walk or paved driveway which is located between two single
family dwellings and serves both dwellings*
** only permitted if veranda, porch, deck, or balcony is fully open on a minimum of 2 sides beneath the  oor*
* as speci ed in CGA B149 Installation Codes, Note: local Codes or Regulation may require different clearances
* for U.S.A. Installations follow the current National Fuel Gas Code, ANSI Z223.1